Thermal rise considerations for laminated busbars in compact cabinets

Nov 2, 2026 · Engineering

Compact cabinets are the norm now. Customers want more power in less space, which means the busbar runs hotter and natural convection has less room to work. A few things I keep in mind when estimating temperature rise.

Start with the current density

For copper busbars in still air, a current density around 1.5–2.0 A/mm² is a reasonable starting point for continuous operation. Go above 2.5 A/mm² and you need to think hard about cooling, especially if the cabinet is sealed or the ambient is above 35 °C.

Surface area matters more than cross-section

Two bars of the same cross-section can have very different temperature rises if one is flat and wide and the other is square. The flat bar has more surface area for the same copper, so it sheds heat better. When space allows, I prefer a wider, thinner bar over a square one.

Watch the joints

The hottest spot is rarely in the middle of a straight run. It is usually at a bolted joint, where contact resistance adds heat. A joint that is torqued correctly and has clean contact surfaces will run only a few degrees above the bar itself. A joint that is loose or dirty can run 20–30 °C hotter, and that is where failures start.

Ventilation

If the cabinet has louvers at the bottom and top, natural convection does a surprising amount of work. Block the top vent with a cable tray and the temperature inside climbs quickly. I always check the vent path on site before signing off.