Creepage distance basics for medium-voltage insulation design
Creepage distance is the shortest path along the surface of an insulator between two conductive parts. It matters because contamination and moisture can create a conductive track along the surface, even if the air clearance is sufficient.
Pollution degree
The required creepage depends on the pollution degree of the environment. Indoor, clean, air-conditioned rooms are pollution degree 1 or 2. Outdoor installations, or indoor sites near a factory floor, are degree 3. The same 10 kV system needs roughly twice the creepage outdoors as it does in a clean indoor room.
Comparative tracking index
Not all insulation materials track equally. The comparative tracking index (CTI) tells you how resistant a material is to forming a conductive path. A material with CTI above 600 is much better than one with CTI of 175. When I specify an insulator, I check the CTI first, then the creepage.
A practical rule
For indoor medium-voltage work, a rough guideline is 20 mm of creepage per kV for pollution degree 2, and 25โ32 mm per kV for degree 3. These are starting points, not substitutes for the standard. Always check IEC 60664 or the relevant product standard for the exact requirement.